Researchers have demonstrated an integrated optimization framework designed to determine optimal recloser placement alongside the simultaneous location and capacity allocation of photovoltaic units across electrical distribution networks. Evaluated using a computational model of the standard IEEE 33-bus test system, the unified methodology directly addresses network reliability challenges that arise when expanding distributed solar generation while operating conventional circuit protection equipment.
Conventional distribution planning approaches traditionally treat the placement of protective devices and the allocation of renewable generation resources as separate engineering problems. In contrast, this study implements a simultaneous formulation to assess how integrating photovoltaic resources influences ongoing protection performance and broader network reliability. Within this optimization structure, the physical placement of reclosers seeks to improve critical reliability indices, specifically system average interruption frequency index, system average interruption duration index, and energy not supplied.
Simultaneously, the framework determines the physical locations and maximum allowable hosting capacity of photovoltaic installations subject to strict network voltage constraints. To preserve operational integrity during fault events, the mathematical formulation integrates coordination constraints between the recloser and downstream cut-out fuses directly into the objective function as a penalty term. This mechanism ensures proper protection coordination throughout the feeder while maintaining the established fuse-saving strategy under transient disturbances.
The authors resolved the multi-objective planning formulation using a specialized search algorithm executed on the simulated IEEE 33-bus distribution system. Under the experimental conditions designated as Scenario 2, the algorithm identified Bus 29 as the optimal connection node for a photovoltaic generation unit. Sizing calculations determined that this node could accommodate a photovoltaic capacity equivalent to 70 percent of the total network load, an allocation that directly resulted in an improved voltage profile across the feeder.
Under the conditions evaluated in Scenario 3, the optimization procedure placed the recloser on Line 1 of the test feeder to maximize protection performance. With this protective configuration established, the simulated reliability metrics yielded an energy not supplied value of 36.82 megawatt-hours per year. Furthermore, the system recorded a system average interruption frequency index of 5.58 interruptions per customer per year alongside a system average interruption duration index of 9.12 hours per customer per year.
Comprehensive short-circuit simulations conducted for fault conditions downstream of the cut-out fuses confirmed that the coordination constraint between the recloser and fuses remained satisfied both with and without photovoltaic integration. These analytical results demonstrate that simultaneously optimizing recloser siting and solar unit sizing successfully expands photovoltaic hosting capacity within established voltage boundaries while preserving the protective fuse-saving strategy. However, the reported numerical improvements and protection balances reflect specific model configurations assessed on the IEEE 33-bus benchmark network rather than field-deployed distribution infrastructure.
Subject of Research: Power distribution network reliability and protection coordination with photovoltaic integration
Article Title: Reliability improvement of distribution networks through optimal recloser placement considering photovoltaic resource allocation and sizing with protection coordination constraints
Article References: Hajiabadi, M. E., Ramezani, H., Tarsa, R., Lotfi, H., & Nejad, M. B. (2026). Reliability improvement of distribution networks through optimal recloser placement considering photovoltaic resource allocation and sizing with protection coordination constraints. Scientific Reports. https://doi.org/10.1038/s41598-026-81218-1
Image Credits: AI Generated
DOI: 10.1038/s41598-026-81218-1
Keywords: distribution networks, recloser placement, photovoltaic resource allocation, photovoltaic sizing, protection coordination, cut-out fuse, fuse-saving strategy, IEEE 33-bus test system, SAIFI, SAIDI, energy not supplied, voltage constraints, hosting capacity, short-circuit analysis, optimization framework, search algorithm, power system reliability
Cite Scienmag News
Reid Dalton. (November 21, 2026). Coordinating Reclosers With Solar Allocation Improves Distribution Grid Reliability in Tests. Scienmag. https://scienmag.com/coordinating-reclosers-with-solar-allocation-improves-distribution-grid-reliability-in-tests/
Reid Dalton. "Coordinating Reclosers With Solar Allocation Improves Distribution Grid Reliability in Tests." Scienmag, 21 November 2026, https://scienmag.com/coordinating-reclosers-with-solar-allocation-improves-distribution-grid-reliability-in-tests/. Accessed 22 November 2026.
Reid Dalton. "Coordinating Reclosers With Solar Allocation Improves Distribution Grid Reliability in Tests." Scienmag. November 21, 2026. https://scienmag.com/coordinating-reclosers-with-solar-allocation-improves-distribution-grid-reliability-in-tests/